4-20 mA Scaling Formula:
From: | To: |
The 4-20 mA scaling formula converts a process variable (like temperature, pressure, etc.) to a standard 4-20 mA current signal used in industrial instrumentation. The 4 mA represents the minimum scale value and 20 mA represents the maximum.
The calculator uses the 4-20 mA scaling formula:
Where:
Explanation: The formula linearly scales the process variable between 4-20 mA, where 4 mA corresponds to the minimum range value and 20 mA corresponds to the maximum range value.
Details: 4-20 mA current loops are widely used in industrial applications because they're less susceptible to noise than voltage signals, can power field devices directly, and provide inherent fault detection (current below 4 mA indicates a problem).
Tips: Enter the current process value and the minimum/maximum range values. The calculator will output the corresponding 4-20 mA current signal. Ensure Max ≠ Min to avoid division by zero.
Q1: Why is 4 mA used as the minimum instead of 0 mA?
A: 4 mA allows for "live zero" detection - if the signal drops below 4 mA, it indicates a fault (broken wire, failed sensor, etc.).
Q2: What's the advantage of current signals over voltage signals?
A: Current signals are less affected by voltage drops over long cable runs and electromagnetic interference.
Q3: Can this formula be used for reverse acting signals?
A: Yes, simply swap the Min and Max values to get a reverse acting signal (20 mA at minimum scale).
Q4: How do I calculate the value from a mA reading?
A: Rearrange the formula: \( Value = Min + \frac{(mA - 4)}{16} \times (Max - Min) \)
Q5: What about 3-wire vs 4-wire transmitters?
A: The calculation is the same regardless of transmitter wiring configuration.